• H07Z-R
  • H07Z-R
  • H07Z-R
  • H07Z-R

H07Z-R

These cables are used for internal wiring of switchboards and distribution boards at AC voltages up to 1000 V or DC voltages up to 750 V. They are generally installed in ducts and are used for internal wiring of equipment with an operating temperature of 90°C. They are suitable for use in public places (such as government buildings, etc.) where smoke and toxic gases may cause threats to life and damage to equipment. This cable does not produce corrosive gases when burned, which is particularly important for electrical equipment. Standards and certifications:
$0.00
Cable parameter:
TUV,CE
TUV,CE
CE
CE
  • H07Z-R
  • H07Z-R

Description

Application and Description:

These cables are used for internal wiring of switchboards and distribution boards at AC voltages up to 1000 V or
DC voltages up to 750 V. They are generally installed in ducts and are used for internal wiring of equipment with
an operating temperature of 90°C. They are suitable for use in public places (such as government buildings, etc.)
where smoke and toxic gases may cause threats to life and damage to equipment. This cable does not produce
corrosive gases when burned, which is particularly important for electrical equipment.
                                                                                                                                                                                                  
Standards and certifications:

HD 22.9 S2, VDE-0282 Part 9, BS 7211, IEC 60754-2, EN 50267, VDE 0482-267,
                                                                                                                                                                                                  

Cable construction:

- Solid bare copper single strand conductor, compliant with IEC 60228 Cl-1 (H05Z-U / H07Z-U)

- Stranded bare copper conductor, compliant with IEC 60228 Cl-2 (H05Z-R)

- Cross-linked polyolefin EI5 insulation

- Core color coding compliant with VDE-0293

- LSOH - Low Smoke Zero Halogen
                                                                                                                                                                                                  

Technical characteristics:

- Working voltage: 300/500v (H05Z-U), 450/750v (H07Z-U / H07Z-R)

- Test voltage: 2500 V

- Dynamic bending radius: 15 x Ø

- Static bending radius: 10 x Ø

- Operating temperature in application: +5º C to +90º C

- Flame retardant: IEC 60332.1

- Insulation resistance: 10 MΩ x km
                                                                                                                                                                                                  

Cable parameters:

Number of cores x conductor cross-sectional area

# x mm²

Nominal insulation thickness mm

Nominal outer diameter mm

Nominal copper weight kg/km

Nominal cable weight kg/km

H07Z-U

1 x 1.5

0.7

2.8

14.4

20

1 x 2.5

0.8

3.3

24

30

1 x 4

0.8

3.8

38

45

1 x 6

0.8

4.3

58

65

1 x 10

1.0

5.5

96

105